Item no.: 8688500

Fillcontrol Auto Compact 8,5

make-up system with pump

Technical data

Type

Auto Compact 8,5

Min. ambient temperature

0 °C

Max. ambient temperature

35 °C

Max. perm. operating temperature

30 °C

Max. perm. operating pressure

10 bar

Max. permissible delivery pressure

8.5 bar

Max. supply pressure

5.5 bar

Inlet/outlet connection

G 3/8" / G 3/8"

Overflow connection

DN32/PN16

Delivery rate

0.12 m³/h

Max. pump rate

0.18 m³/h

Max. electrical rated power

0.70 kW

Min. supply rate

360 l/h

Height

619 mm

Width

579 mm

Depth

287 mm

Weight

19.10 kg

EAN code

4036705114786

Product details

Fillcontrol Auto Compact
Function monitoring of the pressurisation in sealed heating and chilled water systems and controlled make-up of make-up water plus filling function for first filling and refilling. Including controlled replenishment of make-up water and filling function during first filling and refilling.

Particularly suited for systems with low make-up water pressure with CE marking.

Comprising a control unit designed for wall mounting, with a hydraulic part and electronic, ergonomically arranged Control Basic control unit. To protect it against dirt, the unit as a whole is located in a housing made from expanded polypropylene with a removable maintenance cover.

Hydraulic scheme comprises a pressure boosting pump with electronic pressure sensor and integrated system separation for protection of the drinking water according to DIN 1988-100 and EN 1717 by use of an unpressurised water main isolating tank and float valve.

Downloads

Accessories

recommended
Article image

7945723 - Commissioning Fillcontrol Auto/Auto Compact/Smart

Service description:
commissioning of Fillcontrol Auto, Fillcontrol Auto Compact and Fillcontrol Smart by the customer service, comprising:
  • Adjustment of system to the operating parameters specified by the client,
  • Checking the settings and operating parameters, and the system's performance and function in the overall system,
  • All set values documented in a report.

Requirements:

  • The static expansion vessels of all make-up systems must be preset to the pressure specified in the installation and operating instructions.

Customer benefits:
While it is entirely possible for customers to put a recently purchased system into service themselves, there are a number of reasons why commissioning by Reflex is a better idea.

  • Certainty that the system is set up for optimum operation
  • Excluding of possible damage due to incorrect commissioning thus reliability and avoidance of time and costs for downtimes

Commissioning date:
the service can take place within the local country inside about three weeks, internationally within about six weeks after placing of the corresponding order.
Services provided by Service are net! The price does not include any site waiting times or work arising from improper installation or improper condition.

Contact the Reflex Team and further information

Reflex Solutions Pro

  • Free to use
  • Simple and self-explanatory
  • Detailed documentation
Reflex Solutions Pro

Reflex Solutions Pro allows you to design every Reflex and Sinus product into your project quickly and easily. After entering a few system parameters you will receive your custom product solution with all the relevant documentation.