Article image

Item no.: 8810910

Reflexomat Silent Compact RSC 400

compressor controlled pressurisation station, grey, 6 bar

Technical data

Type

RSC 400

Colour

grey

Nominal volume

400 l

Max. useful volume

360 l

Max. permissible system temperature

110 °C

Max. perm. operating temperature

70 °C

Max. perm. operating pressure

6 bar

Max. p0 setting

5.0 bar

Max. sound pressure level

59 dB(A)

Type of protection

IP 54

Connection

G 1"

Electric connection

230V/50Hz

Max. electrical rated power

0.80 kW

Leistung Wärmeerzeuger Heizen Q̇

2000 kW

Leistung Wärmeerzeuger Kühlen Q̇

4000 kW

Diameter

740 mm

Height

1522 mm

High water connection

120 mm

Weight

85.80 kg

EAN code

4036705531248

Product details

Downloads

Accessories

optional
Article image

8894500 - wall mounting bracket 90°

Wall mount for Basic I/O modules and bus modules.
optional
Article image

7613100 - Cap valve SU G1" × 1"

Cap valve
For diaphragm expansion vessels in sealed heating and cooling systems.

With a safe shut-off to prevent inadvertent closing and a discharge according to DIN EN 12828.

optional
Article image

9119352 - motorized ball valve Safecontrol

Safecontrol
Motor ball valve as conversion kit for water make-up in conjunction with Servitec and Variomat.

Actuation takes place directly from the control unit. The dirt-resistant motor ball valve is spring-closed without any need for an electrical supply.

Hydraulic and electrical connections must be made on-site.

optional
Article image

7945726 - Commissioning add. Cat. 3

Service description:
commissioning of an additional system, category 3, for a standard system in the product ranges Reflexomat Compact RSC / Servitec S / Reflex Hydroflow by the customer service, comprising:
  • Adjustment of system to the operating parameters specified by the client,
  • Checking the settings and operating parameters, and the system's performance and function in the overall system,
  • Fillsoft and Fillset are checked too
  • All set values documented in a report.

Requirements:

  • electrical and hydraulic connection of the control unit, the accessory components and filled supply system.
  • The expansion vessels of the pressurisation station must not be filled with water.
  • A sufficient supply of filling water must be provided.
optional
Article image

7857700 - diaphragm rupture detector MBM II

Membrane rupture detector
Electrode with evaluation relay for installation in an expansion vessel with an appropriate connection. Vessel must be pre-equipped for electrode (please note when ordering)

Inclusive of electrode relay for signal measurement for installation in installer-supplied control cabinet or for local installation.

  • power supply 230 V/50 Hz
  • floating output (changeover contact)